Health Inspection Information

The inspection history for the business you selected is displayed below. Each inspection may have zero or more violations. A health inspection report is a "snapshot" of the day and time of the inspection. On any given day, an establishment could have more or fewer violations than noted here. Inspections are based on regulations to eliminate risk factors for illness or injury. Every violation is coded indicating the degree of risk in causing an illness or injury.

  • Critical, Major, or Foodborne Illness Risk Factor Violations: These violations are more likely than other violations to contribute to illness or injury. Inspectors work with operators to make sure that these violations are corrected whenever feasible before they leave the establishment. A re-inspection may be scheduled to verify compliance.
  • Non-Critical, Minor or Good Retail Practice Violations: These violations are not directly related to the cause of illness or injury, but if uncorrected, could negatively affect the operation of the facility, such as maintenance and cleanliness.

Please Note: Tri-County converted to a new database in July 2013. Any inspections listed prior to July 2013 only display the date and type of inspection, but not the inspector comments because of the database conversion. For inspection reports prior to July 2013 please submit a written request to EHInspections@tchd.org.


Facility Details
Program Pool
Facility Name Hampton Inn Brighton
Business Name Hampton Inn Brighton - Pool
Address 992 Platte River Blvd
Brighton, CO 80601-4359
Phone 303-654-8055

Inspection Details
10/06/2021 Inspection, Follow-Up
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The pool and spa free chlorine were both above 5.0 ppm.
09/29/2021 Inspection, Pools Chemical only
01a - Critical
Water Quality: Chemical Quality; Disinfection and pH
Inspector Comments: The swimming pool water free chlorine concentration was 0.0 ppm. The spa water free chlorine concentration was 0.0 ppm. The swimming pool water pH was 7.0.
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The spa water saturation index was 1.1. The swimming pool and spa water contained greater than 100 ppm of cyanuric acid.
02/17/2021 Inspection, Routine
01b - Critical
Water Quality: Water Testing Equipment
Inspector Comments: Five bottles of Taylor chemical test reagents stored on the test kit shelf were expired. There was no thermometer available in the pool pump room to measure water temperature. Corrected on site.
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The spa free available chlorine concentration was 9.6 ppm. The swimming pool saturation index was +0.55. The cyanuric acid concentrations in the pool and spa were both in excess of 100 ppm.
09a - Non-Critical
Deck Areas: Deck Areas
Inspector Comments: The pool and spa skimmers did not have weir gates installed in them.
10a - Non-Critical
Chemicals: Storage and Handling of Chemicals
Inspector Comments: A container of pH Up (base) was stored on top of a container of pH Down (acid) in the pump room.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: The spa heated water return line was not marked with any directional arrows. The spa flow meter did not function. Vacuum gauges were not installed on the pool or spa suction lines prior to the pumps.
11b - Non-Critical
Mechanical Room: Filters
Inspector Comments: The pool and spa sand filters did not have pressure gauges installed.
13a - Non-Critical
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities
Inspector Comments: There was no hose bib available in the pool room or pump room for use in deck washing.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: The swimming pool and spa free chlorine and pH readings were not recorded every day in February, 2021, and when they were recorded, they were recorded only once per day. The pool and spa saturation indexes were not recorded in February, 2021. The spa flow meter reading was not recorded in February, 2021.
14d - Non-Critical
Records and Certifications: CPO or Approved Certification
Inspector Comments: The Certified Pool Operator on record for the facility did not have a current CPO certificate.
09/25/2020 Inspection, Follow-Up
09/23/2020 Inspection, Pools Chemical only
01a - Critical
Water Quality: Chemical Quality; Disinfection and pH
Inspector Comments: The spa pH was 7.0.
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The pool and spa free chlorine levels were above 10 ppm. The spa calcium hardness was 675 ppm.
02/05/2020 Inspection, Routine
09a - Non-Critical
Deck Areas: Deck Areas
Inspector Comments: The pool and spa skimmers were not equipped with weir gates.
10a - Non-Critical
Chemicals: Storage and Handling of Chemicals
Inspector Comments: Bulk pool water balance chemicals were stored within close proximity of the pool water heater.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: Vacuum gauges were not installed on the pool and spa suction lines prior to the circulation pumps. The spa flow meter did not function. The pool backwash line was not marked with a directional flow arrow.
11b - Non-Critical
Mechanical Room: Filters
Inspector Comments: The spa and pool sand filters had pressure gauges installed on the flow selector valves, not on the filters.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: The operator did not record free chlorine and pH every two hours for the spa, and three times per day for the pool. The operator did not record the flow meter reading and saturation index daily for the spa. The operator did not record the pool saturation index on a daily basis.
14d - Non-Critical
Records and Certifications: CPO or Approved Certification
Inspector Comments: The establishment did not have a Certified Pool Operator on staff.
09/30/2019 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The pool free chlorine concentration was above 5.0 ppm.

Please Note: Tri-County converted to a new database in July 2013. Any inspections listed prior to July 2013 only display the date and type of inspection, but not the inspector comments because of the database conversion. For inspection reports prior to July 2013 please submit a written request to EHInspections@tchd.org.