03/24/2021
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The combined chlorine within the spa was 1.8 ppm.
The available free chlorine within the pool was 7.8 ppm.
The total alkalinity of the spa was 25 ppm.
The calcium hardness of the pool was 750 ppm and 925 ppm in the spa.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: An open bag of sodium bicarbonate was stored on the floor of the pool equipment room uncovered.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Vacuum gauges were not present on the raw water lines prior to the pumps on all circulation pumps.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: The disinfectant level and pH were recorded less than three times a day for the pool.
Saturation index, flow meter reading, total alkalinity and calcium hardness were not recorded once a day for the pool.
Cyanuric acid levels were not recorded weekly for the pool.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: A certified pool operator (CPO) or equivalent was not on staff.
|
02/27/2019
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The spa chlorine level was 10ppm. The pool calcium hardness was 850ppm. The pool saturation index was +0.7.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: The pool and spa skimmers did not provide weir gates.
|
09b - Non-Critical |
Deck Areas: Steps, Ladders, Diving |
Inspector Comments: Spa ladder was loose.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The pool flow meter was not functioning. A schematic drawing was not provided for the pump room.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: The spa disinfectant, pH, and temperature were not being recorded every two hours. The pool disinfectant and pH were not being recorded three times a day.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: The facility does not have a CPO certification.
|
04/04/2018
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The pool chlorine was 6ppm. The spa alkalinity was 30ppm.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: A bag of alkalinity chemical by the pump room door was open and not in a sealed container.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: A backflow prevention device was not provided on the hose bib by the pool deck.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: The calcium hardness, alkalinity and saturation index were not being recorded once a day. The pool temperature was not being recorded once a day. The spa temperatures was not being recorded every two hours.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: The facility did not provide a CPO certificate.
|