02/09/2022
Inspection, Pools Chemical only
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: pH in the pool and spa measured below 7.2.
|
01b - Critical |
Water Quality: Water Testing Equipment |
Inspector Comments: The pool test kit available at the facility did not have a means to test for disinfectant level, or pH. Manager of the facility will provide an approved test kit prior to re-opening.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Free chlorine in the pool and spa were above 100ppm. Recommended closure, and pool and spa did close also because of pH imbalance.
|
02/18/2021
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The total alkalinity in the pool and the spa was 60ppm. The saturation index for the pool was -.6. The combined chlorine in the spa was 1.4ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Several areas of the deck were cracked.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: An emergency shutoff switch accessible to bathers was not provided. The spa pump was leaking. The flow meters for the pool and spa were not functioning. Vacuum gauges were not present on the raw water lines prior to the pumps on all circulation pumps.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: An atmospheric vacuum breaker was not present on the deck area wall faucet.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Disinfectant level, and pH were not being recorded three times per day for the pool and every 2 hours for the spa. Flow, temperature, saturation index, total alkalinity, and calcium hardness were not being recorded at least once per day for the pool and spa.
|
02/05/2020
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The free chlorine in the pool was greater than 10ppm. The saturation index of the spa was +.7.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Paint was peeling on the bottom of the pool and spa.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: A main drain cover in the spa was missing. An emergency shutoff switch was not provided to the pool deck area accessible to patrons. A pump for the spa was leaking. The flow meter for the spa was not functioning. Vacuum gauges were not present on the raw water lines prior to the pumps on all circulation pumps.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: A hose bib on the wall near the pool area entrance door was not provided with an atmospheric vacuum breaker.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: A certified pool operator was not able to be associated with the facility during the inspection.
|
03/12/2019
Inspection, Routine
|
01b - Critical |
Water Quality: Water Testing Equipment |
Inspector Comments: The test kit did not have the means to measure alkalinity, and/or calcium hardness. Owner stated a photo will be provided of new test kit by end of day. pH and disinfectant DPD chemical reagents available on site.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The free chlorine residual in the swim pool and spa was above 5.0ppm during the routine inspection.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weirs and/or float valves were not provided to the skimmers of the swim pool or the spa.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Directional arrows were not provided on all plumbing lines.
A complete schematic diagram was not provided.
An emergency shut-down control was not provided.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: A CPO or equivalent was not on staff or under contract.
|
01/16/2018
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: In the spa free chlorine measured higher than 5.0 ppm, combined chlorine measured higher than 1.0 ppm and alkalinity measured less than 70 ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: An emergency shut down control was not located in the deck area or easily accessible.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Flow meters were not operational and turn over rate could not be determined. Water lines in the filtrations systems were not labeled with directional arrows. One of the main drain covers in the main pool was missing. The pool sand filter was observed leaking. A schematic was not provided for the filtration systems in the mechanical room. Skimmers were not provided with weir gates.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: The hose bib in the deck area was not equipped with a backflow preventer.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: At the time of inspection there were not chemical records for the pool (last ones available were dated october 2017).
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: A CPO certificate was not available at the time of inspection.
|
04/06/2017
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: pH in the pool and spa was lower than 7.0 at the time of inspection.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: At the time of inspection free chlorine was higher than 5.0 ppm in the pool and spa and alkalinity was lower than 60 ppm in the pool and spa.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The hose for the automatic chlorinator on the pool filtration system was loose and leaking such that the floor in the mechanical room was pooled with water. A schematic of the filtration systems was not available at the time of inspection. The circulation pipes were not labeled with arrows to indicate direction of flow. An emergency shut-down control was not provided.
|
11b - Non-Critical |
Mechanical Room: Filters |
Inspector Comments: A backwash sight glass was not provided to the spa sand filter.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: Hose bibbs were not provided with a backflow preventer in the deck area.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: No records were available for the pool and spa since december 2016 (only one record for eight days of December available at the time of inspection and it was not marked whether they belonged to the pool or the spa). Records available were not filled according to required chemical readings and frequency (alkalinity, calcium hardness, temperature, turn over rate, saturation index not recorded).
|
12/01/2016
Inspection, Pools Chemical only
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: pH in the pool and spa was less than 7.0 at the time of inspection.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: At the time of inspection: Free chlorine level in the pool and spa were at least 10 ppm, Calcium hardness measured higher than 600 in the pool and spa and Alkalinity was lower than 80 ppm in the pool and spa.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: One drain cover were observed missing in the pool. Drain cover in the spa was not properly attached.
|
08/15/2016
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Calcium hardness was 140 ppm in the pool and 120 ppm in the spa (keep between 150 - 600 ppm)
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Acids and bases were stored together in a shelves rack in the mechanical room. Powdered chemicals (in open permeable bags) were observed stored among (next to and below) containers with liquid chemicals in the shelves rack in the mechanical room.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The filtered water line at the pool filtration system was not color coded green. Water lines were not marked with directional arrows. Flow meter installed in the spa filtration system was not operational at the time of inspection. A schematic diagram of the filtration systems was not provided at the mechanical room.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chemical log was not available for review at the time of inspection.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: A CPO was not on file at the time of inspection.
|
06/10/2015
Inspection, Routine
|
316 - Minor |
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions |
Inspector Comments: No schematic diagram was available for the pool or the spa. The flow meters were not operational.
|
416j - Minor |
Disinfection provided, maintained, proper handling of chemicals:Absorbant chemical containers stored |
Inspector Comments: Chemical powder stored in an absorbent bag was stored directly on the ground.
|
475 - Minor |
Pool chemical parameters must be within required range |
Inspector Comments: The calcium hardness for the spa was below the minimum.
|