02/23/2021
Inspection, Routine
|
01b - Critical |
Water Quality: Water Testing Equipment |
Inspector Comments: Several expired chemical testing reagents were located in the pump room. The facility had alternate chemicals available for testing pool water chemistry at the facility.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Free chlorine in the spa measured 6ppm. The total alkalinity in the pool and spa measured 60ppm.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Vacuum gauges were not present on the raw water lines prior to the pumps on all circulation pumps.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Disinfectant and pH were not being recorded three times per day for the pool, and every 2 hours in the spa. Total alkalinity, calcium hardness, and saturation index were not being recorded once per day for the pool and spa.
|
01/29/2019
Inspection, Routine
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates in the skimmer were missing for the spa and the swim pool.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Acids were stored next to bases (sodium bi sulfate next to soda ash).
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The raw water line of the swim pool and the spa was not color coded yellow.
A pressure vacuum guage was not provided prior to the pump of the swim pool or the spa.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: pH was not recorded at least three times per day
The disinfectant level was not recorded at least three times per day.
The flow meter reading, saturation index, calcium hardness, or the total alkalinity were not recorded daily.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: A CPO or equivalent staff was not on staff or under contract.
|
03/29/2018
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: At the time of inspection, in the pool bromine was higher than 5.0 ppm and saturation index was 0.8, in the spa bromine was higher than 10 ppm, alkalinity was lower than 70 ppm, and temperature was higher than 104°F.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Unfiltered water was labeled green in the mechanical room (should be yellow prior to the filter).
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: pH and disinfectant were not being recorded three times a day for the pool and every two hours for the spa. Alkalinity, calcium hardness and saturation index were not being recorded every day.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: The CPO certification was expired for the CPO in charge.
|
03/02/2017
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: pH for the spa was 7.0 at the time oof inspection. Violation corrected on site.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: At the time of inspection: Bromine was higher than 5.0 ppm in the pool, Alkalinity was 40 ppm in the spa.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The flow meter for the spa filtration system was not operational at the time of inspection.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: pH and disinfectant were being recorded only once a day for the pool and the spa. Alkalinity, calcium hardness, flow rate and saturation index were not being recorded in the chemical log.
|
08/15/2016
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Calcium hardness in the spa was 140 ppm .
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The flow meter in the spa filtration system was not operational at the time of inspection.
|
11d - Non-Critical |
Mechanical Room: Clearance, Floor Drains, Equipment Storage |
Inspector Comments: The floor in the mechanical room was observed wet at the time of inspection.
|
12a - Non-Critical |
Locker rooms, Restrooms, & Bather Control: Locker rooms, Restrooms, & Bather Control |
Inspector Comments: Maximum bather loads were not posted in the swimming area.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Disinfectant and pH were not checked three times a day for the pool. Alkalinity and calcium hardness were not recorded in the chemical log.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: The CPO certificate on file, available at the time of inspection, was expired.
|
04/10/2014
Inspection, Routine
|
316 - Minor |
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions |
Inspector Comments: The piping system in the pump room were not properly color coded.
|
475 - Minor |
Pool chemical parameters must be within required range |
Inspector Comments: The total alkalinity for the spa was lower than 70 ppm. The temperature for the spa was higher than 104°F
|
49 - Minor |
CPO or equivalent; water quality records available; tested at proper frequency; turnover |
Inspector Comments: Pool chemicals were not being checked a minimum of 3 times a day.
|