03/26/2021
Inspection, Routine
|
01b - Critical |
Water Quality: Water Testing Equipment |
Inspector Comments: Multiple testing reagents were expired in the pump room.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Cyanuric Acid was recorded above 100 ppm for the spa and pool.
Free Chlorine in the pool was recorded at 5 ppm.
Total alkalinity was recorded at 60 ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were not provided for the pool and spa.
|
12a - Non-Critical |
Locker rooms, Restrooms, & Bather Control: Locker rooms, Restrooms, & Bather Control |
Inspector Comments: Bather load was not provided in the pool area.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chemical records were not recorded for the spa or pool.
|
03/07/2019
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The combined chlorine for the spa was 4.4ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were not provided on the pool and spa skimmers.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: The pool and spa filter powder did not contain a lid to secure in place and keep dry.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: The chemical logs for the facility were not available to see.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: Facility did not provide a CPO certification.
|
03/08/2018
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The chlorine in both pools was greater than 10 ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were not provided on the skimmers.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: The swim pool filter powder was not sealed with a lid. There was chemical powder all over the floor in the pool room.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The flow meters for the pool and spa were not functioning.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chemical logs were not provided by the facility.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: There is no employee with a CPO license at the facility.
|
03/09/2017
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The pool calcium hardness was lower than the required 150-600ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: The bather load needs to be re-written as it is hard to read. The pool skimmers did not provide weir gates.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: The pool and spa disinfectant and pH were only being checked once a day, as opposed to, three times a day for the pool and every two hours for the spa. The temperature was not being checked once a day for the pool or every two hours for the spa. The saturation index, calcium hardness and flow meter readings were not recorded once daily.
|
05/11/2016
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: The Pool Chlorine was 0.2ppm. The Pool pH level was 7.0.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The calcium hardness of the pool was less than the required 150-600ppm.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The piping to the Spa filter was leaking.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: The coving around the pump room walls was in disrepair.
|
14b - Non-Critical |
Records and Certifications: Turnover Requirements |
Inspector Comments: The turnover rate could not be measured because the flow meters were not in working order.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: The chemical check for the pool and spa were only being done for the Chlorine and pH and were not being done per the requirements of the Regulation.
|
06/04/2015
Inspection, Routine
|
313 - Minor |
NSF, designed, filtration rate, flow meter installed, pressure gauges, backwash line |
Inspector Comments: The flow meters for the pool and spa were not functioning.
|
474 - Major |
Chemical parameters ( Free Chlorine and/or pH) must be within required range; immediate closure |
Inspector Comments: The pH for the pool (7.0) and the spa (6.8) were below 7.2.
|
475 - Minor |
Pool chemical parameters must be within required range |
Inspector Comments: The alkalinity for the spa was 30. The spa temperature (106°) was above 104°. The saturation index for the spa (-.85) was not between -.5 and +.5.
|
04/24/2014
Inspection, Routine
|
312 - Minor |
Filter design, turnover, gauges, backwash sightglass, backwash line, sand specifications, data plate |
Inspector Comments: The pool and spa flow meters were not functioning.
|
475 - Minor |
Pool chemical parameters must be within required range |
Inspector Comments: The pool alkalinity was greater than 180. The pool calcium hardness was less than 150. The spa cyanuric acid was greater than 100. The spa saturation index was greater than +0.5.
|