06/23/2021
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Alkalinity in the baby pool was 50 ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were missing on some skimmers on both bodies of water.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The baby pool had only one main drain provided. Vacuum gauges were not provided on the suction lines prior to the circulation pumps for both bodies of water. Both filtration systems were not color coded and did not have flow arrows provided. The flow meter for the baby pool was not operational. A schematic diagram of both systems was not posted in the mechanical room. The heated water line returning to the main pool was leaking.
|
11b - Non-Critical |
Mechanical Room: Filters |
Inspector Comments: A backwash sight glass was not provided on the main pool backwash line.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: An atmospheric vacuum breaker was not provided on the mens restroom hose bib.
|
14b - Non-Critical |
Records and Certifications: Turnover Requirements |
Inspector Comments: The turnover rate for the main pool was 9.8 hours.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Free chlorine and pH was not recorded 3 times daily for both bodies of water. Alkalinity, calcium hardness, flow meter reading, and saturation index were not recorded once daily for each body of water.
|
07/01/2019
Inspection, Routine
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Both piping systems were not color coded and did not have flow arrows provided. A vacuum gauge was not provided on the suction line prior to the pump for the baby pool. A schematic diagram of the piping system was not posted in the mechanical room. The flow meter for the baby pool was improperly located and was not functioning.
|
11b - Non-Critical |
Mechanical Room: Filters |
Inspector Comments: The back wash line for the main pool did not have a sight glass provided.
|
14b - Non-Critical |
Records and Certifications: Turnover Requirements |
Inspector Comments: The pool turnover was 11.3 hours.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Free chlorine, pH and ORP were not recorded three times daily.
|
06/27/2018
Inspection, Routine
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Horizontal depth markers were not provided on the decks of both pools. The baby pool had only one skimmer provided. Various weir gates were missing on the skimmers for both bodies of water.
|
09b - Non-Critical |
Deck Areas: Steps, Ladders, Diving |
Inspector Comments: 2" color contrasting stripping was not provided on the step entering the baby pool.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The baby pool had only one main drain provided. Emergency shutoffs were not provided in the deck area for both bodies of water. The flow meter for the main pool was not operational. A schematic diagram of the piping system was not posted in the mechanical room.
|
11b - Non-Critical |
Mechanical Room: Filters |
Inspector Comments: A sight glass was not provided on the back wash line for the main pool.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: An atmospheric vacuum breaker was not provided on the hose bib used for filling the baby pool.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: ORP was not recorded 3 times a day. Free chlorine and pH were not recorded 3 times a day. Alkalinity, calcium hardness, and saturation index were not recorded daily.
|
06/14/2017
Inspection, Routine
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were missing on the skimmers for the main pool and baby pool.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Bottles of acid were stored above buckets of chlorine in the pump room.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Emergency shutoffs for both systems were not provided in the pool deck areas. The flow meter for the main pool was not operational. The baby pool only had one main drain.
|
11c - Non-Critical |
Mechanical Room: Chemical and Disinfectant Feeders |
Inspector Comments: The chlorine for the main pool injected prior to the heater.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: The hose bib between the locker rooms and the hose bib behind the fire place did not have atmospheric vacuum breakers provided.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: The disinfectant and pH were not checked 3 times a day for both bodies of water. Alkalinity, hardness, saturation, and flow meter reading were not checked daily for both bodies of water.
|
06/16/2016
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: The free chlorine in the baby pool was less than .4ppm.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Back wash sight glasses were not provided on the back wash lines for the main pool and baby pool. The flow meter on the main pool was not operational.
|
14b - Non-Critical |
Records and Certifications: Turnover Requirements |
Inspector Comments: The baby pool had a turnover rate of 2.8 hrs.
|
07/09/2015
Inspection, Routine
|
301 - Minor |
Surface, shape, design, slopes, depth, depth markers |
Inspector Comments: The wading pool next to the main pool was not fenced in.
|
316 - Minor |
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions |
Inspector Comments: The flow meter on the main pool was not functioning.
|
475 - Minor |
Pool chemical parameters must be within required range |
Inspector Comments: The calcium hardness was above the required maximum level in both pools. The chlorine was above the required maximum level in the wading pool. The cyanuric acid level was below the required minimum level in the main pool.
|
06/03/2014
Inspection, Routine
|
314 - Minor |
NSF, flow rate, pressure gauge, no filter by-pass |
Inspector Comments: The flow meter for the pools were not functional.
|
318 - Minor |
Floor dry; no unnecessarry equipment, chemicals; no unauthorized persons |
Inspector Comments: The floor of the pump room was wet.
|
416b - Major |
Disinfection provided, maintained, proper handling of chemicals: Chemical containers |
Inspector Comments: Large containers of chemicals were stored outside of the pump room with no protection.
|
49 - Minor |
CPO or equivalent; water quality records available; tested at proper frequency; turnover |
Inspector Comments: The pool and wading pool disinfectant and pH were not recorded at least three times a day.
|