06/23/2021
Inspection, Routine
|
01b - Critical |
Water Quality: Water Testing Equipment |
Inspector Comments: Expired pool testing reagents were present in the test kit used for the mens spa.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Alkalinity was 50 ppm for the main pool. Calcium hardness was 125 ppm for the main pool. Saturation index was -.8 for the main pool and baby pool. Free chlorine in the main pool was 6.0 ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were not provided on the skimmers for the main pool and baby pool.
|
09b - Non-Critical |
Deck Areas: Steps, Ladders, Diving |
Inspector Comments: The steps entering the mens spa did not have a two inch color-contrasting strip on the leading edge.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Domestic chemicals (non-commercial grade) were used for maintaining the mens spa.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Vacuum gauges were not provided on the suction lines prior to the pump on all 3 bodies of water. The flow meters for the baby pool and mens spa were not operational. The emergency shutoff for the main pool was in disrepair and not operational. The mens spa did not have an emergency shutoff provided accessible to bathers in the deck area.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: The mop sink faucet used for filling the mens spa did not have an atmospheric vacuum breaker provided. The hose bibs on the water line behind the filters in the main pool pump room did not have atmospheric vacuum breakers provided.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chemical parameter readings were not being recorded for the mens spa. Free chlorine and pH were not recorded 3 times daily for the main pool and baby pool. All other parameters were not recorded daily on all days for the main pool and baby pool.
|
07/11/2019
Inspection, Routine
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were missing on both pool skimmers.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Vacuum gauges were not provided on the suction lines prior to the circulation pumps on both pool piping systems.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Free chlorine and pH were not recorded 3 times daily for each body of water. Saturation index, and flow meter reading were not recorded once daily for each body of water.
|
07/03/2018
Inspection, Routine
|
01b - Critical |
Water Quality: Water Testing Equipment |
Inspector Comments: All reagents in the spa test kit were expired.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The cyanuric acid tested to be over 100ppm in the wading pool.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Horizontal four inch numerals in a contrasting color were not present at the swimming pool, wading pool, or spa.
Vertical four inch numerals in contrasting color were not present at the wading pool, or spa.
Weir gates were not provided on the skimmers for all bodies of water.
Five feet of concrete was not provided around the deck area of the upper swimming pool, wading pool, and spa.
|
09b - Non-Critical |
Deck Areas: Steps, Ladders, Diving |
Inspector Comments: Two inch contrasting color non-slip stripping was not provided on the steps in the swimming pool, or baby pool.
One railing on the pool ladder on the north end of the main pool was loose.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: There were no flow arrows on the baby pool raw water piping.
The flow meters on the spa, and baby pool piping systems were not operational.
The schematic diagrams for the swimming pool, wading pool, and spa piping systems were not posted in the mechanical rooms during inspection.
There was no vacuum gauge provided prior to the pump on all three circulation systems.
An emergency shut off was not provided in the pool deck area or wading pool deck area.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: Atmospheric vacuum breakers were not provided on the hose bib in the pool mechanical room and the hose bib outside the lifeguard station.
|
06/22/2017
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The free chlorine in the spa was greater than 10 ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were missing on the skimmers for the main pool and baby pool. Horizontal and vertical depth markers were not provided on the mens spa. Horizontal depth markers were not provided on the main pool and baby pool.
|
09b - Non-Critical |
Deck Areas: Steps, Ladders, Diving |
Inspector Comments: Two inch color contrasting strips were not provided on the stairs entering the baby pool and upper main pool.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Muriatic acid was stored above chlorine tablets in the main pool chemical storage room.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The flow meters for all three bodies of water were not operational. The flow meters for the main pool and baby pool were improperly located (locate flow meters on the return lines to the pool prior to any chemical injections). Schematic diagrams of the piping systems were not posted for the main pool and baby pool. Emergency shutoffs were not accessible to bathers for the main pool and baby pool.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: The hose bib outside of the guard shack did not have an atmospheric vacuum breaker provided.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Calcium hardness in the spa was 120. The temperature of the spa was 106 F. Calcium hardness, flow meter reading, and saturation index were not checked daily for both pools. Chemical parameters were not checked once every two hours for the spa.
|
06/02/2016
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Calcium hardness on the main pool was 140. Calcium harness on the mens spa was 80.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Horizontal depth markers were not provided on the main pool deck and kidde pool deck. Vertical and horizontal depth markers were not provided on the mens spa.
|
09b - Non-Critical |
Deck Areas: Steps, Ladders, Diving |
Inspector Comments: Color contrasting stripping was not provided on the edges of the stairs entering the kidde pool and upper main pool.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: A flow meter was not provided on the piping system for the main pool. The flow meter for the kidde pool was not operational and was improperly located. The flow meter for the mens spa was not operational. Schematic diagrams were not provided for the piping systems of the main pool, kidde pool, and mens spa. Directional flow arrows were not provided on the raw water line for the kidde pool.
|
12a - Non-Critical |
Locker rooms, Restrooms, & Bather Control: Locker rooms, Restrooms, & Bather Control |
Inspector Comments: Bather load was not posted for the main pool, kidde pool, and mens spa
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: The hose bib on the wall above the main pool piping system was not equipped with an atmospheric vacuum breaker.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chlorine and pH were not checked 3 times daily for the main pool and kidde pool. Alkalinity, hardness, and saturation were not checked daily on the main pool and kidde pool. Chlorine and pH were not checked every 2 hours on the mens spa.
|
06/04/2014
Inspection, Routine
|
316 - Minor |
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions |
Inspector Comments: A schematic diagram was not provided for the pump room. The flow meter for the wading pool was not functional.
|
416e - Major |
Disinfection provided, maintained, proper handling of chemicals:Liquid chemicals by dry chemicals |
Inspector Comments: Liquid chemicals were stored above dry chemicals in the chemical store room.
|
416g - Major |
Disinfection provided, maintained, proper handling of chemicals: Chemicals stored above eye level |
Inspector Comments: Chemicals were stored above eye level in the chemical store room.
|
475 - Minor |
Pool chemical parameters must be within required range |
Inspector Comments: The temperature of the main pool was 74°F. The chlorine for the wading pool was 10ppm.
|