Health Inspection Information

The inspection history for the business you selected is displayed below. Each inspection may have zero or more violations. A health inspection report is a "snapshot" of the day and time of the inspection. On any given day, an establishment could have more or fewer violations than noted here. Inspections are based on regulations to eliminate risk factors for illness or injury. Every violation is coded indicating the degree of risk in causing an illness or injury.

  • Critical, Major, or Foodborne Illness Risk Factor Violations: These violations are more likely than other violations to contribute to illness or injury. Inspectors work with operators to make sure that these violations are corrected whenever feasible before they leave the establishment. A re-inspection may be scheduled to verify compliance.
  • Non-Critical, Minor or Good Retail Practice Violations: These violations are not directly related to the cause of illness or injury, but if uncorrected, could negatively affect the operation of the facility, such as maintenance and cleanliness.

Please Note: Tri-County converted to a new database in July 2013. Any inspections listed prior to July 2013 only display the date and type of inspection, but not the inspector comments because of the database conversion. For inspection reports prior to July 2013 please submit a written request to EHInspections@tchd.org.


Facility Details
Program Pool
Facility Name Eaglecrest High School
Business Name Eaglecrest High School
Address 5100 S Piccadilly St
Aurora, CO 80015-3300
Phone

Inspection Details
10/26/2021 Inspection, Pools Chemical only
03/02/2021 Inspection, Routine
01b - Critical
Water Quality: Water Testing Equipment
Inspector Comments: Expired pool testing reagents were present in the pool test kit used by the facility.
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: Alkalinity in the pool was 250 ppm. The pool saturation index was +.8.
10a - Non-Critical
Chemicals: Storage and Handling of Chemicals
Inspector Comments: Bags of sodium bisulfate were stored next to bags of soda ash in the mechanical room.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: The emergency shutoff switch for the pool was not easily accessible, as it was located in the mechanical room. A vacuum gauge was not provided on the suction line prior to the circulation pump.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: Free chlorine, pH and ORP were not recorded 3 times daily.
02/27/2020 Inspection, Routine
01b - Critical
Water Quality: Water Testing Equipment
Inspector Comments: Various pool testing reagents in the mechanical room were expired.
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The free chlorine in the lap pool was 5.6.
10a - Non-Critical
Chemicals: Storage and Handling of Chemicals
Inspector Comments: Bags soda ash were stored next to bags of sodium bisulfate in the mechanical room.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: A vacuum gauge was not provided on the suction line prior to the pump. The suction line prior to the pump was not color coded yellow and did not have flow arrows provided.
12a - Non-Critical
Locker rooms, Restrooms, & Bather Control: Locker rooms, Restrooms, & Bather Control
Inspector Comments: Soap was not provided at the locker room showers.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: Free chlorine, pH and ORP were not recorded 3 times daily on all days.
10/31/2019 Inspection, Pools Chemical only
02/11/2019 Inspection, Routine
01b - Critical
Water Quality: Water Testing Equipment
Inspector Comments: One bottle of pH indicator in the pump room test kit expired 1/2019.
10a - Non-Critical
Chemicals: Storage and Handling of Chemicals
Inspector Comments: Bags of sodium bisulfate were stored in between bags of soda ash and sodium thiosulfate in the pump room.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: A vacuum gauge was not provided on the suction line prior to the circulation pump. The emergency shutoff switch was located in the pump room.
11e - Non-Critical
Mechanical Room: Make-Up Water and Cross Connections
Inspector Comments: A shutoff switch was present downstream of the atmospheric vacuum breaker on the hose bibb nearest the womens locker room.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: Free chlorine, pH, and ORP were not recorded three times daily on some days.
10/22/2018 Inspection, Pools Chemical only
04/05/2018 Inspection, Routine
10a - Non-Critical
Chemicals: Storage and Handling of Chemicals
Inspector Comments: Bags of sodium bisulfate were stored next to bags of soda ash in the mechanical room.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: The emergency shutoff for the circulation system was not accessible to bathers due to its location in the locked mechanical room.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: Chlorine, pH, and ORP were not checked 3 times daily on all days.
11/01/2017 Inspection, Pools Chemical only
03/16/2017 Inspection, Routine
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: An emergency shutoff was not provided in the pool deck area.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: Saturation index and flow meter reading were not checked daily.
09/29/2016 Inspection, Pools Chemical only
05/10/2016 Inspection, Routine
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: Chlorine and pH readings were not taken 3 times daily.
12/02/2015 Inspection, Pools Chemical only
11/04/2015 Inspection, Routine
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The calcium hardness level in both the diving pool and the lap pool measured 140 and shall be maintained between 150 to 600.
09a - Non-Critical
Deck Areas: Deck Areas
Inspector Comments: The concrete floor was in disrepair next to the lap pool rail. The concrete floor was pitted near the handicap accessible chair at the lap pool.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: A schematic diagram was not posted in the pump room. The lap pool and diving pool flow meters were not operational.
14d - Non-Critical
Records and Certifications: CPO or Approved Certification
Inspector Comments: A CPO certificate was not provided at the facility.
11/24/2014 Inspection, Pools Chemical only
05/13/2014 Inspection, Routine
316 - Minor
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions
Inspector Comments: No schematic diagram was posted in the pump room.

Please Note: Tri-County converted to a new database in July 2013. Any inspections listed prior to July 2013 only display the date and type of inspection, but not the inspector comments because of the database conversion. For inspection reports prior to July 2013 please submit a written request to EHInspections@tchd.org.