06/03/2021
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The temperature of the pool waster was 75°F.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Deck drains were not provided for the pool.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Both flow meters for the kids and adult pools were not functioning.
Vacuum gauges were not installed on the suction line prior to both pumps.
The main pool only had one main drain.
An emergency shutdown was not provided in an area accessible to bathers.
|
12a - Non-Critical |
Locker rooms, Restrooms, & Bather Control: Locker rooms, Restrooms, & Bather Control |
Inspector Comments: Soap was not provided to the locker room showers.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: Verification of an approved CPO or equivalent was not able to be provided at the time of inspection.
|
06/04/2019
Inspection, Routine
|
01b - Critical |
Water Quality: Water Testing Equipment |
Inspector Comments: Chemical R0011L, R-0008, R-0007, and R-0004 were expired during the inspection. Replacements for these chemicals were available on site.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The free chlorine residual of the swim pool and wading pool was above 5.0ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were not present in the swim pool or wading pool.
4 inch contrasting color depth markers were not present on vertical or horizontal walls for the wading pool.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Flow meter for the swim pool and wading pool were non functioning.
Wading pool had one main drain.
|
12a - Non-Critical |
Locker rooms, Restrooms, & Bather Control: Locker rooms, Restrooms, & Bather Control |
Inspector Comments: Showers were not provided soap in mens and womens bathrooms.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chemical records were not available for the wading pool or swim pool as connection to digiquatics was unavailable at time of inspection.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: A CPO certification was not available during the routine annual inspection.
|
07/11/2018
Inspection, Routine
|
03a - Critical |
Water Supply and Wastewater: Waste Disposal |
Inspector Comments: The method of sewage disposal for the facility was not in accordance with the requirements of the colorado department of health as the backwash line leads to two pipes one leading to a storage tank and the other leading to the grass outside the fence.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Depth markers with 4 inch numerals of contrasting color on horizontal or vertical walls were missing from the wading pool.
Weirs and/or float valves in the skimmers of wading and swim pools were missing.
Two skimmers were not provided to the wading pool.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Two maindrains were not provided to the wading or swim pools.
|
11b - Non-Critical |
Mechanical Room: Filters |
Inspector Comments: The backwash sight glass was not provided to the sand filter to the wading or swim pool.
|
07/14/2016
Inspection, Routine
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Chemicals in permeable bags were observed stored directly on the floor in the disinfectant and base storage room.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The newly replaced piping at the mechanical room was not color coded and marked with directional arrows.
|
14b - Non-Critical |
Records and Certifications: Turnover Requirements |
Inspector Comments: The pool turnover was 17 hours (observed flow rate was 50 GPM at the time of inspection) . The wadding pool turnover was 1.5 hours (observed flow rate was 40 GPM at the time of inspection).
|
06/08/2015
Inspection, Routine
|
301 - Minor |
Surface, shape, design, slopes, depth, depth markers |
Inspector Comments: No contrasting deck markings on vertical walls at the main pool. No contrasting deck markings on the vertical or horizontal walls at the wading pool.
|
316 - Minor |
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions |
Inspector Comments: The pipeline for the main pool heated water was not color coded. The pipeline for the wading pool filtered water was not color coded. Several pipes in the piping system were missing directional arrow labels. A flow meter was not available for the wading pool piping system at the time of inspection.
|
322 - Minor |
Minimum number provided, construction; minimum water temperature 90 F; proper lighting |
Inspector Comments: No soap was provided for dressing room showers at the time of inspection.
|
323 - Minor |
Proper number of swimmers allowed: Proper number of swimmers allowed |
Inspector Comments: Pool maximum capacity was not posted.
|
37 - Minor |
Handrails, ladders, steps, stairs provided; tread non-slip, color contrasting; starting blocks |
Inspector Comments: Handrail at the south east corner of the main pool was not securely attached.
|
411a - Major |
Disinfection provided, maintained, proper handling of chemicals: Automatic chlorinator required |
Inspector Comments: An employee was observed adding chemical into the pool while occupied.
|
474 - Major |
Chemical parameters ( Free Chlorine and/or pH) must be within required range; immediate closure |
Inspector Comments: The wading pool had a pH of 6.8.
|
475 - Minor |
Pool chemical parameters must be within required range |
Inspector Comments: Wading pool had Alkalinity of 30 ppm and saturation index -1.25
|
06/09/2014
Inspection, Routine
|
301 - Minor |
Surface, shape, design, slopes, depth, depth markers |
Inspector Comments: Depth markers were not provided to the wading pool.
|
312 - Minor |
Filter design, turnover, gauges, backwash sightglass, backwash line, sand specifications, data plate |
Inspector Comments: The wadding pool flow meter was not functioning.
|
37 - Minor |
Handrails, ladders, steps, stairs provided; tread non-slip, color contrasting; starting blocks |
Inspector Comments: The ladder on the east side of the 5 feet deep was loose.
|
416j - Minor |
Disinfection provided, maintained, proper handling of chemicals:Absorbant chemical containers stored |
Inspector Comments: A bag of absorbent chemicals were stored on the floor of the storage shed.
|
49 - Minor |
CPO or equivalent; water quality records available; tested at proper frequency; turnover |
Inspector Comments: The turnover rate is at 8.3 hours.
|
08/01/2013
Inspection, Pools Chemical only
|
4111 - Minor |
Showers for all bathers required; soap provided; |
Inspector Comments: Soap was not provided to hand sinks and showers in the men's and women's restrooms.
|
412 - Major |
Sewer adequate for facility; all wastes discharge through air gap; discharge to sanitary sewer only |
Inspector Comments: The back wash line drains out onto the south side of the pool to the park grass, and not to a sanitary sewer. Must be corrected by opening day 2014.
|
49 - Minor |
CPO or equivalent; water quality records available; tested at proper frequency; turnover |
Inspector Comments: The turn over rate was 9.25 hours.
|