Health Inspection Information

The inspection history for the business you selected is displayed below. Each inspection may have zero or more violations. A health inspection report is a "snapshot" of the day and time of the inspection. On any given day, an establishment could have more or fewer violations than noted here. Inspections are based on regulations to eliminate risk factors for illness or injury. Every violation is coded indicating the degree of risk in causing an illness or injury.

  • Critical, Major, or Foodborne Illness Risk Factor Violations: These violations are more likely than other violations to contribute to illness or injury. Inspectors work with operators to make sure that these violations are corrected whenever feasible before they leave the establishment. A re-inspection may be scheduled to verify compliance.
  • Non-Critical, Minor or Good Retail Practice Violations: These violations are not directly related to the cause of illness or injury, but if uncorrected, could negatively affect the operation of the facility, such as maintenance and cleanliness.

Please Note: Tri-County converted to a new database in July 2013. Any inspections listed prior to July 2013 only display the date and type of inspection, but not the inspector comments because of the database conversion. For inspection reports prior to July 2013 please submit a written request to EHInspections@tchd.org.


Facility Details
Program Pool
Facility Name Ravenna Fitness Center
Business Name Ravenna Fitness Center
Address 11118 Caretaker Rd
Littleton, CO 80125-9128
Phone 303-566-2859

Inspection Details
07/20/2021 Inspection, Pools Chemical only
01a - Critical
Water Quality: Chemical Quality; Disinfection and pH
Inspector Comments: The free chlorine available within the spa was less than .2 ppm. The spa was closed for one turn over, the inspector verified that the free chlorine available was greater than .4 ppm prior to the end of the inspection. No re-inspection required.
07/07/2021 Inspection, Routine
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: The facility is not recording cyanuric acid weekly. The facility is not recording calcium hardness daily.
14d - Non-Critical
Records and Certifications: CPO or Approved Certification
Inspector Comments: A certified pool operator certificate was not available for review at the time of inspection.
07/30/2020 Inspection, Pools Chemical only
06/16/2020 Inspection, Pools Chemical only
08/15/2019 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The cyanuric acid of the swim pool and spa was above 100ppm.
05/15/2019 Inspection, Routine
01a - Critical
Water Quality: Chemical Quality; Disinfection and pH
Inspector Comments: The pH of the spa was 8.4.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: The pool circulation pump must be the Pentair Whisperflo 3 HP. Vacuum guages must be provided on the suction lines prior to the circulation pumps for the pool and spa.

Please Note: Tri-County converted to a new database in July 2013. Any inspections listed prior to July 2013 only display the date and type of inspection, but not the inspector comments because of the database conversion. For inspection reports prior to July 2013 please submit a written request to EHInspections@tchd.org.


Search Again