Health Inspection Information

The inspection history for the business you selected is displayed below. Each inspection may have zero or more violations. A health inspection report is a "snapshot" of the day and time of the inspection. On any given day, an establishment could have more or fewer violations than noted here. Inspections are based on regulations to eliminate risk factors for illness or injury. Every violation is coded indicating the degree of risk in causing an illness or injury.

  • Critical, Major, or Foodborne Illness Risk Factor Violations: These violations are more likely than other violations to contribute to illness or injury. Inspectors work with operators to make sure that these violations are corrected whenever feasible before they leave the establishment. A re-inspection may be scheduled to verify compliance.
  • Non-Critical, Minor or Good Retail Practice Violations: These violations are not directly related to the cause of illness or injury, but if uncorrected, could negatively affect the operation of the facility, such as maintenance and cleanliness.

Please Note: Tri-County converted to a new database in July 2013. Any inspections listed prior to July 2013 only display the date and type of inspection, but not the inspector comments because of the database conversion. For inspection reports prior to July 2013 please submit a written request to EHInspections@tchd.org.


Facility Details
Program Pool
Facility Name Safe Splash
Business Name Safe Splash
Address 5930 S Gun Club Rd
Aurora, CO 80016
Phone 303-799-1885

Inspection Details
10/07/2021 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The calcium hardness was 650 in the small pool and 700 in the main pool. The saturation index in both pools was +.9.
03/23/2021 Inspection, Routine
01b - Critical
Water Quality: Water Testing Equipment
Inspector Comments: Expired pool testing reagents were present in the mechanical room.
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The saturation index for both pools was -.7.
09a - Non-Critical
Deck Areas: Deck Areas
Inspector Comments: Weir gates were missing on the skimmers for both pools.
10a - Non-Critical
Chemicals: Storage and Handling of Chemicals
Inspector Comments: Bags of thiosulfate and sodium bicarbonate were stored uncovered in the mechanical room.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: The backwash lines for each pool were mislabeled yellow instead of the required black. Both mechanical systems were not properly color coded (yellow from pool suction to pool filters, green from filters to heaters, red from heaters to pool). Vacuum gauges were not provided on the suction lines prior to the circulation pumps on both systems. The flow meter for the small pool was not functioning.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: Saturation index and flow meter reading were not recorded daily for each pool. Calcium hardness was not recorded daily on all days.
14d - Non-Critical
Records and Certifications: CPO or Approved Certification
Inspector Comments: A certified pool operator was not provided on staff.
12/14/2020 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The calcium hardness in the main pool was greater than 600 ppm. The calcium hardness in the wading pool was greater than 600 ppm.
09/01/2020 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The alkalinity in the large pool was 225 ppm. The calcium hardness in both pools was greater than 600 ppm.
12/03/2019 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: Calcium hardness was greater than 600 ppm in both pools.
04/12/2019 Inspection, Follow-Up
04/03/2019 Inspection, Routine
01b - Critical
Water Quality: Water Testing Equipment
Inspector Comments: Alkalinity, thiosulfate, and DPD1 were expired in the blue test kit.
09a - Non-Critical
Deck Areas: Deck Areas
Inspector Comments: Weir gates were missing on the skimmers for both pools.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: Both piping systems were not color coded (suction lines from pool up to filter should be colored yellow. Filtered water lines from the filter to the heater should be colored green. Heated water lines from the heater to the pool should be colored red. Backwash lines should be colored black). The flow meters for both systems were not operational. Vacuum gauges were not provided on the suction lines prior to the pumps on both systems. Schematic diagrams of both systems were not posted in the mechanical room.
13a - Non-Critical
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities
Inspector Comments: A shutoff (spray nozzle) was present on the hose downstream of the atmospheric vacuum breaker on the hose bibb nearest the pump room.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: Free chlorine, pH, and ORP were not recorded three times a day on all days for the small pool. Saturation index was not recorded daily for the small pool.
10/22/2018 Inspection, Pools Chemical only
01a - Critical
Water Quality: Chemical Quality; Disinfection and pH
Inspector Comments: The free chlorine level in the main pool was .2 ppm. The pH in the small pool was greater than 8.0.
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The calcium hardness in both pools was greater than 600 ppm. The alkalinity in the small pool was 50.
10/22/2018 Inspection, Follow-Up
03/06/2018 Inspection, Routine
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: Saturation index for the main pool was +.7. Alkalinity for the main pool was 190. Alkalinity for the baby pool was 50. Calcium hardness for the main pool was greater than 600.
09a - Non-Critical
Deck Areas: Deck Areas
Inspector Comments: Weir gates were not provided on the skimmers for both pools.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: The filtration system piping was incorrectly color coded for both filtration systems (suction lines from the skimmers and main drains to the filters should be yellow, piping from the filters to the heater should be green, piping from the heater to the pool should be red, and backwash lines should be black). The flow meters for both pools were not operational.
11b - Non-Critical
Mechanical Room: Filters
Inspector Comments: Backwash sight glasses were not provided on the filters or the back wash lines.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: Chlorine, pH, and ORP were not checked three times a day on all days for both bodies of water. Calcium hardness was not checked once a day on both bodies of water. Saturation index was not checked once a day for both bodies of water.
11/07/2017 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The calcium hardness was greater than 600 ppm in both bodies of water (Maintain at 150-600). The saturation index was greater than +.5 in both bodies of water (maintain at -.5 - +.5).
03/16/2017 Inspection, Routine
01b - Critical
Water Quality: Water Testing Equipment
Inspector Comments: One bottle of alkalinity 1 was expired.
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: Calcium hardness on the large pool was 980, and on the small pool 780. Alkalinity on the small pool was 210. Saturation index on the large pool was +.9, and on the small pool +.8.
09a - Non-Critical
Deck Areas: Deck Areas
Inspector Comments: Weir gates were not provided on the skimmers for both pools.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: The color coding for both piping systems was incorrect, and flow arrows were not provided on all sections of piping (raw water from pump to filter yellow, filtered water from pump to heater green, heated water red, backwash lines black).
11b - Non-Critical
Mechanical Room: Filters
Inspector Comments: Sight glasses were not provided on the backwash lines or on the filters.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: Flow meter reading and saturation index were not recorded once daily.
11/29/2016 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The calcium hardness on the big pool was 1000. The calcium hardness on the small pool was 960. The saturation index on the big pool was +1.2. The saturation index on the small pool was +.8.
04/07/2016 Inspection, Routine
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The calcium hardness for the small pool measured 1120 and 800 for the lap pool (maintain between 150-600). The saturation index for the lap pool measured +0.8 (maintain between -0.5 to +0.5).
09a - Non-Critical
Deck Areas: Deck Areas
Inspector Comments: Pool capacities for both pools were not posted.
11/02/2015 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The total alkalinity of the lap pool measured 400 ppm. The saturation index of the lap pool measured +0.7.
03/05/2015 Inspection, Routine
316 - Minor
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions
Inspector Comments: A schematic diagram of the pump room was not available. Neither the flow meter for the big pool or small pool were in operation.
475 - Minor
Pool chemical parameters must be within required range
Inspector Comments: The calcium hardness exceeded the maximum limit of 600ppm in both pools. The saturation index exceeded the ideal range of -0.5-0.5.
49 - Minor
CPO or equivalent; water quality records available; tested at proper frequency; turnover
Inspector Comments: Chemical records were not kept up to date: disinfectant and pH levels were not being recorded at least three times a day for the pools. Alkalinity, calcium hardness, and saturation index were not being recorded at least once a day on a regular basis for both pools.
09/05/2014 Inspection, Pools Chemical only
475 - Minor
Pool chemical parameters must be within required range
Inspector Comments: The total alkalinity was 200ppm for both pools. The calcium hardness was greater than 600ppm for both pools. The saturation index was 1.0 for the large pool and 0.8 for the small pool.
03/20/2014 Inspection, Routine
314 - Minor
NSF, flow rate, pressure gauge, no filter by-pass
Inspector Comments: The large pool flow meter was not functioning correctly.
4111 - Minor
Showers for all bathers required; soap provided;
Inspector Comments: Soap was not provided to the showers.
475 - Minor
Pool chemical parameters must be within required range
Inspector Comments: The total alkalinity of the pool was 20. The calcium hardness of the pool was 920 and the small pool was 840.

Please Note: Tri-County converted to a new database in July 2013. Any inspections listed prior to July 2013 only display the date and type of inspection, but not the inspector comments because of the database conversion. For inspection reports prior to July 2013 please submit a written request to EHInspections@tchd.org.