01/21/2021
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: The pH in the swimming pool was above 8 at the beginning of the inspection. The pH was checked at the end of the inspection and was balancing out to approximately 7.8 - 8. Pool operator is continuously monitoring the level, and pool was covered and out of use at time of inspection.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The free chlorine in the pool was 5.6ppm (recommend 1-3ppm). The saturation index in the pool was +.7.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: 4" horizontal and vertical depth markers were not provided on the swimming pool deck.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: A vacuum gauge was not provided on the suction line prior to the pump. The flow meter on the return line was not functioning. An emergency shutoff accessible to users of the pool was not provided.
|
11b - Non-Critical |
Mechanical Room: Filters |
Inspector Comments: The pressure gauge on the front sand filter was not functioning. Both sand filters were not provided with a backwash sight glass.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: The faucet on the pool deck was not provided with a hose bib atmospheric vacuum breaker backflow device.
|
03/03/2020
Inspection, Routine
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: The pool walls and deck were not marked with 4-inch depth markers. The skimmer on the east side of the pool did not have a weir gate.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The pool heated water line leading into the water heater did not have a directional arrow. The pool did not have an emergency shutoff for the pumps. The flow meter did not function.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: The pool make up water was provided by a hose attached to a hose bib with no atmospheric vacuum breaker backflow prevention.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: The pool total alkalinity and calcium hardness were recorded sporadically not once per day. The pool flow meter reading, saturation index, and water temperature were not recorded on the chemical records.
|
02/21/2019
Inspection, Routine
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Four (4) inch numerals in a contrasting color were not provided on the deck of the pool.
Four (4) inch numerals in a contrasting color were not provided on the vertical wall of the pool.
The pool skimmers did not have weir gates.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The pool flow meter was not functioning. Both raw water lines from pump to filter were not color coded yellow. Both raw water lines from pump to filter did not have directional arrows.
|
12a - Non-Critical |
Locker rooms, Restrooms, & Bather Control: Locker rooms, Restrooms, & Bather Control |
Inspector Comments: The women's shower was not provided with soap.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chemical records were not available on site at the time of inspection.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: The pool did not have a certified pool operator.
|
02/22/2018
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Calcium Hardness was 110.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Four (4) inch numerals in a contrasting color were not provided on the deck of the pool.
Four (4) inch numerals in a contrasting color were not provided on the vertical wall of the pool.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The pool flow meter was not functioning.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chemical records were not available upon request during the inspection.
|
01/27/2017
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The saturation index was +0.6.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: The pool did not have 4 inch contrasting depth markers on vertical and horizontal walls. The skimmers did not have weir gates.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The flow meter was not functioning.
|
12a - Non-Critical |
Locker rooms, Restrooms, & Bather Control: Locker rooms, Restrooms, & Bather Control |
Inspector Comments: The hose bib by the men's restroom did have an atmospheric vacuum breaker.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chlorine and pH were not checked and recorded three times daily. The flowmeter reading, temperature, saturation index, calcium hardness and total alkalinity were not checked and recorded daily.
|