07/21/2021
Inspection, Pools Chemical only
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: The swimming pool and wading pool pH were both 6.8.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The swimming pool free chlorine was 6.0 ppm, the total alkalinity was 50 ppm, the saturation index was -0.8, and the cyanuric acid concentration was above 100 ppm.
The wading pool pH was 6.8, the total alkalinity was 50 ppm, the water temperature was 75 degrees F, the saturation index was -0.85, and the cyanuric acid concentration was above 100 ppm.
|
07/02/2021
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The pool water temperature was 75 degrees F.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: The swimming pool skimmers did not have weir gates installed in them. The wading pool did not have skimmers.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Liquid muriatic acid containers were stored directly above bags of powdered sodium bicarbonate (base) on the chemical storage shelving.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The swimming pool and wading pool each had one main drain. The flow meter did not function.
|
06/10/2019
Inspection, Routine
|
01b - Critical |
Water Quality: Water Testing Equipment |
Inspector Comments: Numerous bottles of Taylor pool water test reagents were expired. Corrected on site.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: The swimming pool skimmers were not provided with weir gates.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Bottles of liquid algaecide and muriatic acid were stored next to bags of sodium bicarbonate on the floor pallet in the pump room.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The flow meter did not function. There was not a vacuum gauge installed on the suction line upstream of the pump. Both the wading pool and the swimming pool had one main drain. There was no emergency pump system shutoff switch accessible to bathers.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Free chlorine and pH levels were recorded one to two times per day, rather than three times per day. The operator did not record the flow meter reading and saturation index on any days since opening the pool for the season.
|
06/27/2018
Inspection, Routine
|
01b - Critical |
Water Quality: Water Testing Equipment |
Inspector Comments: Three bottles of Taylor pool test reagents were expired, corrected on site.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Containers of liquid muriatic acid were stored above sacks of soda ash on the chemical storage shelves.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The main pool and wading pool each had one main drain. The flow meter did not function, so the turnover rate could not be calculated.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chlorine and pH were the only readings taken each day, and they were taken once per day rather than 3 times per day. Calcium hardness and total alkalinity were recorded sporadically in the month of June, 2018. Readings for cyanuric acid, flow meter, saturation index, and water temperature were not recorded in June, 2018.
|
06/14/2017
Inspection, Routine
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The raw water piping in the pump room was colored blue, but should be colored yellow. The piping lines were not all marked with directional arrows. The main pool and wading pool each had one main drain.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: The pool water temperature, flow meter reading, and saturation index were not recorded once per day.
|
07/05/2016
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: The pH was 7.0 in the swimming pool and the wading pool.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: The swimming pool deck did not have depth markers. The swimming pool and wading pool capacities were not posted.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Chemicals in absorbent containers were stored on the floor in the pump room.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Both the swimming and wading pools had one main drain.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chlorine and pH were checked once per day. Three times per day is required. Total alkalinity, calcium hardness, temperature, turnover rate, and saturation index were not recorded.
|