07/26/2018
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: The pH of the upper splash pad tested to be under 7.0 during the routine inspection. TCHD asked for the upper splash pad to be closed until the pH tested to be a minimum of 7.2. During the inspection the upper splash pad was re-tested to read 7.6 ppm. TCHD authorizes the re-opening of the upper splash pad during the routine inspection.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The calcium hardness of the splash pad tested to be 125ppm during the routine inspection which is under the minimum required of 150ppm.
The temperature of the upper and lower splash pads tested to be under 77 degrees F. The upper splash pad tested to be 70 degrees F and the lower splash pad tested to be 63 degrees F.
The saturation index of the upper splash pad tested to be -1.0 during the routine inspection; above the maximum of -0.5.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Muriatic Acid was stored with insecticides in the mechanical room. This was corrected during the inspection.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The raw water line of the upper splash pad was not color coded yellow.
An emergency shut down control for the upper and lower splash pads were not provided.
The chemical feeder was functioning but was leaking water.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: The free chlorine residual and the pH of the lower splash pad were not recorded three times daily.
|
06/18/2015
Inspection, Routine
|
316 - Minor |
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions |
Inspector Comments: The flow meters in both pump rooms were not operational.
|
318 - Minor |
Floor dry; no unnecessarry equipment, chemicals; no unauthorized persons |
Inspector Comments: The floor in the lower pump room was soiled with water.
|
49 - Minor |
CPO or equivalent; water quality records available; tested at proper frequency; turnover |
Inspector Comments: The turn over rate for both splash pads could not be calculated because the flow meters were not operational.
|
07/11/2014
Inspection, Routine
|
316 - Minor |
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions |
Inspector Comments: The pipes in both pump rooms were not color coded correctly.
|
318 - Minor |
Floor dry; no unnecessarry equipment, chemicals; no unauthorized persons |
Inspector Comments: The floor in the lower pump room was wet.
|
49 - Minor |
CPO or equivalent; water quality records available; tested at proper frequency; turnover |
Inspector Comments: Alkalinity, calcium hardness, and saturation index were not being measured daily, as indicated by chemical records. Turnover rate could not be measured due to unknown capacity of the fountains.
|