04/22/2021
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The alkalinity in the Womens warm pool was 50ppm.
The free chlorine in the Womens cold pool was 10ppm.
The saturation index in the Womens cold pool was -.7.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Several pool pump lines for the Mens and Womens pools were not color coded.
Vacuum gauges were not present on the raw water lines prior to the pumps on all circulation pumps.
The flow meters for the Mens and Womens pools were not functioning.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: Hose bibs in the Mens and Womens spa area were not provided with atmospheric vacuum breakers.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Disinfectant and pH were not being recorded three times per day for the pools. Alkalinity, calcium hardness, temperature, and saturation index were not being recorded daily for the pools.
|
04/03/2019
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: The disinfectant level of the mens hot tub and cold tub was 0.0ppm. The pH of the womens large hot tub was above 8.0ppm. TCHD has closed the mens hot tub, cold tub, and womens large hot tub until one full turnover as well as a re-inspection has occurred by TCHD staff.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The saturation index of the womens large hot tub was 0.6.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: The weirs in the skimmer were missing for all bodies of water.
|
09b - Non-Critical |
Deck Areas: Steps, Ladders, Diving |
Inspector Comments: The womens large hot tub walk in ladder rail was loose.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Muriatic acid was stored next to bases.
|
11b - Non-Critical |
Mechanical Room: Filters |
Inspector Comments: A vacuum guage was not present on the pumps of any filtration system.
|
02/15/2018
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: The mens hot pool contained less than .4ppm free chlorine. The pH of the mens and womens hot pools was above 8.0.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Calcium hardness in the mens hot pool and the womens hot pools was lower than 150 ppm. The free chlorine in the mens and womens cold pools were greater than 5 ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were not provided on the skimmers for all bodies of water.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The flow meter for the mens hot pool was not operational. A flow meter for the mens cold pool was not provided. The raw water piping from the mens hot pool pump to the filter was not color coded yellow. The existing schematics for the filtration systems were not clearly labeled and did not have the required information and ability to distinguish between filtration systems. Two filtration systems for the womens room were not equipped with flow meters and turn over could not be determined at the time of inspection.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: The hose bibs in the mens pool area and womens pool area did not have atmospheric vacuum breakers provided.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chemical records were not available at the time of inspection.
|
10/04/2017
Inspection, Follow-Up
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: Free chlorine in the women's cold pool was below the required 0.4 ppm (measured 0.2 ppm) at the time of inspection. pH in the men's spa measured less than the required 7.2 (measured 7.0). Violations corrected on site.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Free chlorine measured 10 ppm after correcting for low chorine.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Chemicals in the mechanical room were not observed stored in their original containers (observed in empty detergent containers) and lacking their original label.
|
10/03/2017
Inspection, Pools Chemical only
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: At the time of inspection: 1. in the women's area, bromine was lower than 2.0 ppm in the big and small spa pools and pH was higher than 8.0 in the big spa pool. 2. In the men's area, there was no free available bromine in the hot tub. The pH in the mens cold spa was 7.1.
|
01c - Critical |
Water Quality: Turbidity |
Inspector Comments: Turbidity in the mens hot tub was unacceptable due to the addition of chemicals.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: At the time of inspection free chlorine measured higher than 5. 0 ppm (50 ppm in a test strip) in the waterfall pool. In the womens area, the three bodies of water measured calcium hardness lower than 150 ppm. The chlorine in the mens cold pool was above 10 ppm. Allkalinity in the cold mens spa was 50. Calcium hardness in the cold mens spa was 100, calcium hardness in the hot mens spa was 80. Saturation index for the hot mens spa was +.6, saturation index for the cold mens spa was -1.0.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chemical records were not available, and the last date chemicals were checked was November 12th 2016 as stated by operator.
|
03/28/2017
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: The pH in the mens cold pool was 6.7 (corrected on site to 7.9). The free available bromine in the mens hot pool was 0.45. pH for the women cold pool was less than 6.8 and bromine for the two women spas was 0.2 ppm. (Bromine levels in womens corrected on site to 4.5 ppm) (Bromine in mens hot pool was corrected to 4.0). Both mens pools may reopen.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Alkalinity in the mens cold pool was 30. Free chlorine in the mens cold pool was greater than 5.0. Calcium hardness in the mens cold pool was 120. Saturation index in the mens cold pool was -1.6. The calcium hardness for the mens hot pool was 100. Alkalinity for the cold women pool was 40 ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were not provided on the skimmers for the mens hot pool and mens cold pool.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Bather load was not posted for the mens or womens pools.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The flow meter for the mens hot pool was broken. A flow meter for the mens cold pool was not provided. The heated water for the mens cold pool was not color coded red. The mens cold pool had only one main drain. Flow meters for the women filtration system were not operational. A shut-off emergency control was not provided for the women's pool area.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: Atmospheric vacuum breakers were not provided on the two hose bibs in the mens pool area.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Records of chemical parameters were not provided on site.
|
14d - Non-Critical |
Records and Certifications: CPO or Approved Certification |
Inspector Comments: A Certified Pool Operator was not provided.
|
05/26/2016
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: Ph for both men and women areas were lower than 6.8. In the men area, the cold pool had a free chlorine concentration of 0.2
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Alkalinity in the women cold pool and and small spa was 30 ppm. Alkalinity in the men cold pool was 20 ppm. (alkalinity must be 70 - 180 ppm). Calcium hardness in the women pools were lower than the required 150 ppm (cold pool was 120, spa were 100). Saturation index for the women cold pool was -1.45 and for the men cold pool was less than -1.5
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Flow meters in the mechanical room were not operational.
|
11d - Non-Critical |
Mechanical Room: Clearance, Floor Drains, Equipment Storage |
Inspector Comments: The floor at the mechanical room was observed wet (water pooled). A permeable bag with pool chemicals was observed stored directly on the floor.
|
05/13/2015
Inspection, Routine
|
312 - Minor |
Filter design, turnover, gauges, backwash sightglass, backwash line, sand specifications, data plate |
Inspector Comments: A sight glass was not provided for the backwash line on the mens' hot or cold spa filters.
|
316 - Minor |
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions |
Inspector Comments: The flow meters for the mens' hot and cold spa were not operational.
|
475 - Minor |
Pool chemical parameters must be within required range |
Inspector Comments: Alkalinity in the mens' cold spa was 60 ppm. Calcium hardness in the mens' hot and cold spa was 140 ppm.
|
49 - Minor |
CPO or equivalent; water quality records available; tested at proper frequency; turnover |
Inspector Comments: The Certified Pool Operator (CPO) under contract did not have a certificate readily available on-site. The establishment did not maintain adequate records for alkalinity and hardness levels.
|
07/22/2014
Inspection, Routine
|
316 - Minor |
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions |
Inspector Comments: Not all pump piping systems were labeled and color coded. The flow meters were not functioning on all five spa systems.
|
323 - Minor |
Proper number of swimmers allowed: Proper number of swimmers allowed |
Inspector Comments: The spa capacities for the women's spas were not posted.
|
37 - Minor |
Handrails, ladders, steps, stairs provided; tread non-slip, color contrasting; starting blocks |
Inspector Comments: The ladder handle on the steps of the women's large hot spa was loose.
|
474 - Major |
Chemical parameters ( Free Chlorine and/or pH) must be within required range; immediate closure |
Inspector Comments: The men's hot spa bromine disinfectant was 0.45. Spa is closed. Men's cold spa pH was 6.8. Spa is closed.
|
475 - Minor |
Pool chemical parameters must be within required range |
Inspector Comments: The men's cold spa and the men's hot spa total alkalinity was 50. The men's cold spa and the men's hot spa calcium hardness was 100. The men's cold spa saturation index was -1.5. The women's hot spa large total alkalinity was 30. The women's cold spa total alkalinity was 60. The women's hot spa large calcium hardness was 60. The women's hot spa calcium hardness was 100. The women's cold spa calcium hardness was 120. The women's hot spa large saturation index was -1.1.
|
49 - Minor |
CPO or equivalent; water quality records available; tested at proper frequency; turnover |
Inspector Comments: Up to date chemical records were not being kept.
|