06/24/2019
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: The baby pool did not provide any chlorine disinfectant.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The main pool saturation index was -0.6. The baby pool alkalinity was 60ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Several floor tiles were missing in the water entry way of the wading pool. 4 inch depth markers were not present on the inside of the big pool or the wading pool. Weir gates were not provided in the wading pool skimmers.
|
09b - Non-Critical |
Deck Areas: Steps, Ladders, Diving |
Inspector Comments: All diving well step ladders were loose. The big pool step ladders were loose.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Vacuum gauges were not provided on the suction line prior to the pump for the big pool or the baby pool. The emergency stop for the big pool and wading pool was located inside the pump room and was not accessible.
|
12a - Non-Critical |
Locker rooms, Restrooms, & Bather Control: Locker rooms, Restrooms, & Bather Control |
Inspector Comments: Soap was not provided in the women's showers.
|
14b - Non-Critical |
Records and Certifications: Turnover Requirements |
Inspector Comments: The main pool turnover rate was 6.6 hours. The baby pool turnover rate was 33 minutes.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: The saturation index and flow meter were not being recorded daily for the big pool or the wading pool.
|
06/14/2018
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Total alkalinity for the large and dive pool was 50 ppm. The saturation index was -0.6.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: An emergency shut off switch was not accessible for any bodies of water.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Flow meter reading and saturation index was not checked and recorded daily.
|
07/17/2017
Inspection, Routine
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: The floor by the large pool heater was wet. The floor by the wading pool pump was wet.
|
12a - Non-Critical |
Locker rooms, Restrooms, & Bather Control: Locker rooms, Restrooms, & Bather Control |
Inspector Comments: The women's showers were not provided with soap.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Saturation index and flow meter reading were not checked and recorded daily.
|
07/15/2014
Inspection, Routine
|
316 - Minor |
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions |
Inspector Comments: The flow meter for the wading pool was not functioning.
|
475 - Minor |
Pool chemical parameters must be within required range |
Inspector Comments: The temperature of the wading pool was below the required minimum of 77°F
|
49 - Minor |
CPO or equivalent; water quality records available; tested at proper frequency; turnover |
Inspector Comments: The turnover rate for the lap pool was greater than 6 hours.
|