06/21/2021
Inspection, Routine
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were not provided to the pool skimmers.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: A bottle of muriatic acid was stored on top of a bucket of pool shock.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Several pool pump lines were not properly color coded with directional flow arrows.
The flow meter for the pool was not functioning.
A vacuum gauge was not installed on the suction line prior to the pump.
An emergency shutdown was not provided to the deck area accessible to pool users.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: The pool filling hose bib on the pool deck was not provided with an atmospheric vacuum breaker.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: The facility was not testing and recording pH and disinfectant 3 times per day as required.
|
06/26/2019
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The free chlorine for the pool was greater than 10ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Four inch numerals in contrasting color were not provided to the horizontal deck of the pool.
Weir gates were not provided on the pool skimmers.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: An open bag of calcium chloride was stored with other chemicals in the pump room.
Liquid Sea Klear and Pool Perfect were stored directly above dry calcium chloride and sodium bicarbonate in the pump room.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The flow meter for the pool was not functioning, and was installed on the suction line instead of the proper placement on the return line.
Directional flow arrows were not provided on the pool pump lines.
An emergency shut-off switch was not provided accessible to pool users.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: A hose bib outside of the south pump room door was not provided with an atmospheric vacuum breaker.
|
07/13/2018
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: TCHD asked for closure of the pool due to low pH.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The free chlorine residual tested to be 12.6 during inspection.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Horizontal 4 inch depth markers of contrasting color were not provided to the deck area.
Weirs and/or float valves were missing from the skimmers.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The maindrain cover was not secured. TCHD recommends closure until maindrain is secured.
|
11d - Non-Critical |
Mechanical Room: Clearance, Floor Drains, Equipment Storage |
Inspector Comments: The floors in the mechanical room did not slope to the floor drains; puddling was observed during the inspection.
|
13a - Non-Critical |
Cleaning, Premises Maintained: Hose Bibbs, Pool Cleaning Equipment, Clean Facilities |
Inspector Comments: An atmospheric vacuum breaker was not supplied to the hose bib outside of the mechanical room.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chlorine and pH were not recorded three times daily.
The saturation Index and flow meter reading were not recorded daily.
|
06/27/2017
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: pH was lower than 7.2 at the time of inspection.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: At the time of inspection free chlorine was higher than 5 ppm and alkalinity was lower than 70 ppm.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: At the time of inspection the flow meter was not operational. An emergency shut-down was not provided.
|
06/16/2016
Inspection, Routine
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Calcium hardness was 140 ppm (min 150 max 600 recommended 200 - 400). Saturation index was -0.6 (min & max +/- 5.0 recommended +/- 2.0)
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Chemicals were stored in the mechanical room (both bases and acids)
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The flow meter was not operational at the time of inspection.
|
11d - Non-Critical |
Mechanical Room: Clearance, Floor Drains, Equipment Storage |
Inspector Comments: The floor at the mechanical room was observed wet at the time of inspection.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Calcium hardness and saturation index were not recorded daily. Disinfectant and pH were not checked three times a day.
|