Health Inspection Information

The inspection history for the business you selected is displayed below. Each inspection may have zero or more violations. A health inspection report is a "snapshot" of the day and time of the inspection. On any given day, an establishment could have more or fewer violations than noted here. Inspections are based on regulations to eliminate risk factors for illness or injury. Every violation is coded indicating the degree of risk in causing an illness or injury.

  • Critical, Major, or Foodborne Illness Risk Factor Violations: These violations are more likely than other violations to contribute to illness or injury. Inspectors work with operators to make sure that these violations are corrected whenever feasible before they leave the establishment. A re-inspection may be scheduled to verify compliance.
  • Non-Critical, Minor or Good Retail Practice Violations: These violations are not directly related to the cause of illness or injury, but if uncorrected, could negatively affect the operation of the facility, such as maintenance and cleanliness.

Please Note: Tri-County converted to a new database in July 2013. Any inspections listed prior to July 2013 only display the date and type of inspection, but not the inspector comments because of the database conversion. For inspection reports prior to July 2013 please submit a written request to EHInspections@tchd.org.


Facility Details
Program Pool
Facility Name Quality Inn
Business Name Comfort Inn
Address 10535 E Diente Ct
Englewood, CO 80112
Phone 303-858-9900

Inspection Details
08/31/2021 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The total alkalinity of the pool was 50ppm.
04/13/2021 Inspection, Follow-Up
04/12/2021 Inspection, Follow-Up
01a - Critical
Water Quality: Chemical Quality; Disinfection and pH
Inspector Comments: The free chlorine available within the spa was .2 ppm.
04/01/2021 Inspection, Routine
01a - Critical
Water Quality: Chemical Quality; Disinfection and pH
Inspector Comments: The free chlorine available in both the pool and spa was 0 ppm.
01b - Critical
Water Quality: Water Testing Equipment
Inspector Comments: Several testing reagents were expired in the pump room. The facility had unexpired reagents available on site.
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The calcium hardness for the pool was 50 ppm. The saturation index of the pool was -.94.
09a - Non-Critical
Deck Areas: Deck Areas
Inspector Comments: Weir gates were not in place or in good working order on both the pool and the spa.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: The flow meter for both the spa and pool was not functioning. The vacuum gauge on the spa raw water line was not functioning and the vacuum gauge on the pool raw water line was missing.
11b - Non-Critical
Mechanical Room: Filters
Inspector Comments: A sight glass on the backwash line of both the pool and spa was not available.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: The disinfectant level and pH was not recorded 3 times a day for both the pool and spa. The water temperature was not recorded every 2 hours for the spa. The Saturation index, total alkalinity, and calcium hardness were not record daily for both the pool and spa. The cyanuric acid levels were not recorded weekly for both the pool and spa.
14d - Non-Critical
Records and Certifications: CPO or Approved Certification
Inspector Comments: A Certified Pool Operator (CPO) was not on staff.
08/27/2020 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The pool temperature was 76°F. The free chlorine available within the pool was 8.6 ppm. The total Calcium Hardness within the pool was 775 ppm. The saturation index was + 1.25 .
03/12/2020 Inspection, Routine
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The free chlorine residual in the spa was above 5.0ppm.
09a - Non-Critical
Deck Areas: Deck Areas
Inspector Comments: Weir gates were not present in the swim pool or spa.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: The flow meter for the spa and swim pool pump systems were non functioning.
11b - Non-Critical
Mechanical Room: Filters
Inspector Comments: The pressure gauges on the sand filter of the spa and swim pool pump systems were not in working order.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: The pH and free chlorine residual were not checked three times a day. The combined chlorine, total alkalinity, calcium hardness, flow meter reading, and saturation index were not checked daily.
14d - Non-Critical
Records and Certifications: CPO or Approved Certification
Inspector Comments: A certified pool operator was not available to the facility.
03/21/2019 Inspection, Routine
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The pool chlorine was 5.8ppm. The pool combined chlorine was 2.0ppm. The spa combined chlorine was 1.2ppm. The spa calcium hardness was 125ppm. The pool cyanuric acid was greater than 100.
09a - Non-Critical
Deck Areas: Deck Areas
Inspector Comments: Weir gates were not provided on the pool or spa skimmers.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: Spa flow meter was not functioning.
11b - Non-Critical
Mechanical Room: Filters
Inspector Comments: A sight glass was not provided on the spa sand filter.
11/08/2018 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The spa calcium hardness was 125ppm. The spa temperature was 105°F.
03/08/2018 Inspection, Routine
01b - Critical
Water Quality: Water Testing Equipment
Inspector Comments: Several chemical bottles were expired.
09a - Non-Critical
Deck Areas: Deck Areas
Inspector Comments: Weir gates were not provided on all skimmers.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: A schematic drawing was not provided in the pump room.
14b - Non-Critical
Records and Certifications: Turnover Requirements
Inspector Comments: The spa turnover rate was 40 minutes, as opposed to the required, 30 minutes.
12/13/2017 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The calcium hardness in the pool and spa was less than the required 150-600ppm.
02/16/2017 Inspection, Routine
09a - Non-Critical
Deck Areas: Deck Areas
Inspector Comments: Weir gates were not provided on the spa/pool skimmers.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: The flow meter for the pool was stuck. A schematic drawing was not posted in the pump room.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: Saturation index was not being recorded once a day.
11/29/2016 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The Bromine in the pool was greater than the maximum 5.0ppm. The temperature in the spa was greater than the required maximum of 104 degrees Fahrenheit. The calcium hardness in the pool and spa was not in the required range of 150 to 600ppm.
09/07/2016 Inspection, Routine
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: Calcium hardness was less than the required 150-600ppm.
11a - Non-Critical
Mechanical Room: Recirculation System, Piping, and Maindrains
Inspector Comments: The spa flow meter was not functioning.
14c - Non-Critical
Records and Certifications: Chemical Records Maintained
Inspector Comments: The pool and spa were only being checked once a day. The facility was not recording the saturation index, the calcium hardness, the flow rate or the alkalinity once a day.
11/10/2015 Inspection, Pools Chemical only
08a - Non-Critical
Water Quality; Other: Water Quality; Other
Inspector Comments: The calcium hardness in the pool and spa was below the required 150-600.
07/28/2015 Inspection, Follow-Up
07/21/2015 Inspection, Routine
316 - Minor
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions
Inspector Comments: A schematic diagram of the pump room was not available.
318 - Minor
Floor dry; no unnecessarry equipment, chemicals; no unauthorized persons
Inspector Comments: The floor of the pump room had standing water.
37 - Minor
Handrails, ladders, steps, stairs provided; tread non-slip, color contrasting; starting blocks
Inspector Comments: The handrails for the pool steps and ladder were loose.
416j - Major
Disinfection provided, maintained, proper handling of chemicals:Absorbant chemical containers stored
Inspector Comments: A bag of powder calcium chloride was being stored on the floor in the chemical storage closet.
474 - Major
Chemical parameters ( Free Chlorine and/or pH) must be within required range; immediate closure
Inspector Comments: The chlorine level in the spa (.2) was below the required .4. The spa pH (7.0) was not between 7.2-8.0.
475 - Minor
Pool chemical parameters must be within required range
Inspector Comments: The spa alkalinity (220) was not between 70-180.
49 - Minor
CPO or equivalent; water quality records available; tested at proper frequency; turnover
Inspector Comments: The facility does not have a CPO on staff or under contract.
08/06/2014 Inspection, Pools Chemical only
475 - Minor
Pool chemical parameters must be within required range
Inspector Comments: The saturation index on the pool was not between -0.5 to 0.5, as required. The alkalinity of the spa was less than the required 70-180.
03/13/2014 Inspection, Routine
316 - Minor
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions
Inspector Comments: The pump room did not provide a schematic drawing of the pumping systems.
318 - Minor
Floor dry; no unnecessarry equipment, chemicals; no unauthorized persons
Inspector Comments: The floor of the pump room was wet.
474 - Major
Chemical parameters ( Free Chlorine and/or pH) must be within required range; immediate closure
Inspector Comments: The spa temperature was 106°F, as opposed to the required, 77°F-104°F. Bromine in the spa was 1.125ppm, as opposed to the required, 2ppm -10ppm bromine. The calcium hardness for the pool and the spa was 80ppm and 60ppm, respectively, as opposed to the required, 150-600ppm.
49 - Minor
CPO or equivalent; water quality records available; tested at proper frequency; turnover
Inspector Comments: Chemicals in the pool were not being tested three times a day. Chemicals in the spa were not being tested every two hours.

Please Note: Tri-County converted to a new database in July 2013. Any inspections listed prior to July 2013 only display the date and type of inspection, but not the inspector comments because of the database conversion. For inspection reports prior to July 2013 please submit a written request to EHInspections@tchd.org.