03/02/2021
Inspection, Routine
|
01b - Critical |
Water Quality: Water Testing Equipment |
Inspector Comments: One expired DPD titrant was present in the pool test kit used by the facility.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Alkalinity in the pool was 50 ppm. Calcium hardness in the pool was 650 ppm. The free chlorine in the spa was greater than 5.0 ppm.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were not provided on the pool and spa skimmers. The spa was provided with only one skimmer.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The flow meters for the pool and spa were not operational. A schematic diagram of both piping systems was not posted in the mechanical room. Vacuum gauges were not provided on the pool and spa suction lines prior to the circulation pumps.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chemical parameter records were not present onsite.
|
03/09/2020
Inspection, Routine
|
01b - Critical |
Water Quality: Water Testing Equipment |
Inspector Comments: One expired pool testing reagent was stored in the mechanical room.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The alkalinity in the pool was 50.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were not provided on the pool and spa skimmers.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The spa had only one skimmer provided. Vacuum gauges were not provided on the suction lines prior to the pump for both the pool and spa circulation pumps.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Free chlorine, temperature, and pH were not recorded once every two hours for the spa. Flow meter reading and saturation index were not recorded daily for the spa. ORP was not recorded 3 times daily for the pool. Flow meter reading and saturation index were not recorded daily for the pool.
|
01/31/2019
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: The spa pH was below 7.0.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: The combined chlorine in the spa was 4.2 ppm. The free chlorine in the pool was 6.2. The alkalinity in the spa was 50.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Only one skimmer was provided for the spa. Weir gates were not provided on the pool and spa skimmers.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The flow meters for the spa filtration system were improperly located and were not functioning. The flow meter for the pool filtration system was not functioning.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chemical records were not available at the facility for the pool or spa.
|
02/07/2018
Inspection, Routine
|
01b - Critical |
Water Quality: Water Testing Equipment |
Inspector Comments: Two expired testing bottles of sodium thiosulfate were present in the mechanical room.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Alkalinity in the pool was 40.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were not provided on the pool and spa skimmers.
|
10a - Non-Critical |
Chemicals: Storage and Handling of Chemicals |
Inspector Comments: Separate measuring scoops for each chemical were not provided.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: The spa flow meter was improperly located (locate flow meters on an 8 foot section of pipe downstream of the heater, and prior to any chemical injections). A schematic drawing of the pool and spa piping systems was not posted in the mechanical room. The circulation pump for the spa leaked.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Spa chemical parameters were not checked every two hours, pool chemical parameters were not checked three times a day. For the spa, check chlorine and pH every two hours, all other parameters once a day. For the pool check chlorine and pH three times a day, all other parameters once a day.
|
01/18/2017
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: The pH on the spa was 7.0.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Alkalinity in the pool was 60. Alkalinity in the spa was 30. Saturation index on the spa was -.6. The spa temperature was 105 F.
|
09a - Non-Critical |
Deck Areas: Deck Areas |
Inspector Comments: Weir gates were not provided on the pool and spa skimmers.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: Schematic diagrams of the pool and spa piping systems were not posted. The flow meter for the spa was installed in an incorrect location (flow meters should be placed on the heated water line prior to injection of chemicals, and away from elbows).
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: The following chemical parameters were not checked daily for both bodies of water: saturation index, flow meter reading, calcium hardness, alkalinity. Chlorine and pH were not checked every two hours on the spa. Chlorine and pH were not checked 3 times daily on the pool.
|
05/04/2016
Inspection, Routine
|
01a - Critical |
Water Quality: Chemical Quality; Disinfection and pH |
Inspector Comments: The pH in the spa was 6.8.
|
08a - Non-Critical |
Water Quality; Other: Water Quality; Other |
Inspector Comments: Alkalinity in the pool was 40 ppm. Saturation index in the pool was -.7. Calcium hardness in the spa was 140. Alkalinity in the spa was 20.
|
11a - Non-Critical |
Mechanical Room: Recirculation System, Piping, and Maindrains |
Inspector Comments: A schematic diagram was not posted in the pump room.
|
14c - Non-Critical |
Records and Certifications: Chemical Records Maintained |
Inspector Comments: Chemical records were not taken 3 times daily for the pool and spa on 5/3/16.
|
06/17/2014
Inspection, Routine
|
312 - Minor |
Filter design, turnover, gauges, backwash sightglass, backwash line, sand specifications, data plate |
Inspector Comments: The flow meter on the spa and pool were not operating.
|
316 - Minor |
Color coded pipes & arrows; guages & flow meter installed; schematic diagram posted, instructions |
Inspector Comments: A schematic diagram of the pump room was not provided. The pipes in the pump room were not color coded.
|
475 - Minor |
Pool chemical parameters must be within required range |
Inspector Comments: The temperature of the spa was 107 degrees F. The total alkalinity of the spa was 50 ppm. The calcium hardness of the pool was 120 ppm. The calcium hardness of the spa was 80 ppm.
|